Views: 1116

Measurement and Control Datalogger CR6

Product code : 1684121033

The CR6 Measurement and Control Datalogger is a powerful core component for your data-acquisition system. The CR6 datalogger provides fast communication, low power requirements, built-in USB, compact size, and high analog input accuracy and resolution. It uses universal (U) terminals to allow a connection to virtually any sensor—analog, digital, or smart. This multipurpose data logger is also capable of doing static vibrating wire measurements.

Quantity:
More information:
  • Nhà Sản Xuât
  • CAMPBELL SCIENTIFIC, INC.

    Specifications:

    Operating Temperature Range
    • -40° to +70°C (standard)
    • -55° to +85°C (extended)
    • Non-condensing environment
    Maximum Scan Rate 1000 Hz
    Case Material High-impact-resistant polycarbonate and UV-resistant TPE, recycle code 7
    Analog Inputs Up to 12 single-ended or 6 differential (The CR6 has 12 universal [U] and 4 control [C] terminals that can be programmed for a variety of functions. The number of analog inputs, switched excitations, and digital ports assume all the ports are configured the same.)
    Universal Inputs 12 individually configured inputs for analog or digital functions
    Pulse Counters 16 (C1 to C4 and U1 to U12)
    Communications Ports
    • Ethernet
    • USB Micro B
    • CS I/O
    • CPI
    • RS-485
    • RS-422
    • SDI-12
    Data Storage Ports microSD
    Switched 12 Volt 2 terminals
    Digital I/O 16 terminals (C1 to C4, U1 to U12) configurable for digital input and output. Terminals are configurable in pairs for 5 V or 3.3 V logic for some functions.
    Input Limits ±5 V
    Analog Voltage Accuracy
    • Accuracy specifications do not include sensor or measurement noise.
    • ±(0.04% of measurement + offset) at 0° to 40°C
    • ±(0.06% of measurement + offset) at -40° to +70°C
    • ±(0.08% of measurement + offset) at -55° to +85°C (extended temperature range)
    ADC 24-bit
    Power Requirements
    • 16 to 32 Vdc for charger input (CHG) (Current limited at 12 Vdc to 1.2 A at 20°C maximum.)
    • 10 to 16 Vdc for battery input (BAT) (Current limited at 12 Vdc to 2.5 A maximum at 20°C.)
    Real-Time Clock Accuracy ±3 min. per year (optional GPS correction to ±10 µs)
    Internet Protocols Ethernet, PPP, RNDIS, ICMP/Ping, Auto-IP (APIPA), IPv4, IPv6, UDP, TCP, TLS (v1.2), DNS, DHCP, SLAAC, Telnet, HTTP(S), SFTP, FTP(S), POP3/TLS, NTP, SMTP/TLS, SNMPv3, CS I/O IP, MQTT
    Communication Protocols CPI, PakBus, SDM, SDI-12, Modbus, TCP, DNP3, UDP, NTCIP, NMEA 0183, I2C, SPI, and others
    Battery-backed SRAM for CPU Usage & Final Storage 4 MB
    Data Storage 4 MB SRAM + 72 MB flash (Storage expansion of up to 16 GB with removable microSD flash memory card.)
    Idle Current Drain, Average
    • Assumes 12 Vdc on BAT terminals; add 2 mA if using CHG terminals.
    • < 1 mA
    Active Current Drain, Average
    • Assumes 12 Vdc on BAT terminals; add 2 mA if using CHG terminals.
    • 3 mA (1 Hz scan)
    • 67 mA (20 Hz scan)
    Static Vibrating Wire Measurements Supported
    Dimensions 21.0 x 10.2 x 5.6 cm (8.3 x 4.0 x 2.2 in.)
    Additional clearance required for cables and leads.
    Weight 0.42 to 0.52 kg (0.92 to 1.15 lb) depending on communication option selected

Related Products

Updating
VIDEO
Lingerie Fashion